Electrical power/ CALCULATOR

Single-phase AC load current

Convert real input power, voltage and power factor into apparent power and approximate steady current.

Use measured input power or the relevant manufacturer input rating—not useful heat or mechanical output.
Use the voltage expected at the load during operation.
Use documented or measured power factor. Enter 100% only for a near-resistive load.
A transparent scenario allowance, not a universal breaker-sizing rule.
Approximate apparent power

2,316 VA

Estimated steady current

10.07 A

Current including allowance

12.59 A

Single-phase sinusoidal AC, steady RMS voltage, stated real input power and power factor, and one load. Starting current, harmonics, waveform, duty cycle, efficiency, voltage variation, conductor ampacity, breaker characteristics and local rules are excluded. Do not select a cable or protective device from this result alone.